The isolation module D9057M is used to protect the bus in the event of a short-circuit fault. When a short-circuit fault occurs somewhere on the bus, the isolator module adja-cent to the short-circuit will act quickly and cut off the short-circuited part, thus ensur-ing that other devices on the bus can work normally. When the short-circuit fault is removed, the isolation chassis will be de-isolated and the isolated part of the device will be re-connected to the bus. The isolation module D9057M does not need to be addressed and does not occupy an address in the loop.
Operating voltage | 20V – 28V (mains voltage) |
---|---|
Static current | <85uA |
Isolation current | < 9mA |
Indicator | Yellow(remains on during isolation and off during monitoring) |
Operating temperature | -10 to 55°C. |
Relative humidity | ≤95% (40°C±2°C non-condensing) |
Terminal wiring capacity | 0.2mm2 ~1.5mm2 |
External dimensions | 45×26 x 17mm |