Fire Alarm Control Panel (FACP) SEC1000
Features
- Up to 120 addresses on one loop;
- The loop supports class A and Class B types;
- An easy to read, 4.3’’ color screen LCD with a resolution of 480×272;
- Zone indicators for 16 zones gives a quick indica-tion of the location of an alarm;
- Record capacity of 1000 historical events for each of historical fire, historical fault and histori-cal operation;
- An independently programmable conventional sounder circuit output;
- Zone test, point test and module start/stop test-ing facilitate the commissioning;
- Hierarchy management with three access levels;
- CAN bus for interconnection of up to 20 FACPs;
The purpose of the Fire Alarm Control Panel (FACP) SEC1000 is to monitor input signals, give indications and possibly activate outputs as programmed. SEC1000 is designed to comply with EN 54-2 with
qualities of simple installation, operation and easy maintenance.
Mains supply | 110V/230VAC (-15%, +10%),50Hz/60Hz |
---|---|
Mains fuse | T3.15AL250V |
Operating voltage | 20 ~ 28VDC |
Recommended mains cable | Standard/black mains cable, cable size 0.75mm2 |
Power rating | Imin=0.45A; Imax.a=1.15A; Imax.b=1.65A |
Max. battery supply current | 3A (when the Mains is disconnected) |
Max. charging current | 1A |
Battery capacity, type and recommended model | NP7-12 for 7Ah VRLA(Yuasa) |
Max. internal resistance of battery | 1Ω |
Battery fuse | F6AL250V |
Quiescent current (full loaded) | < 0.4A |
S.C.Out (+,-) - Output voltage | 20 ~ 28VDC |
S.C.Out (+,-) - Max. output current | 800mA, 1A S.C.Out+24VK in total |
S.C.Out (+,-) - End of line resistor | 47K ohm 0.25W |
S.C.Out (+,-) - Recommended type of cable | Plain unscreened cable, 1.5mm2 |
S.C.Out (+,-) - Cable diameter | 1mm2~ 2.5mm2 |
S.C.Out (+,-) - Transmission distance | ≤1500m |
F.A.Out(+,-) - Output voltage | 20 ~ 28VDC |
F.A.Out(+,-) - Max. output current | 100mA |
F.A.Out(+,-) - End of line resistor | 47K ohm 0.25W |
F.A.Out(+,-) - Recommended type of cable | Plain unscreened cable, 1.5mm2 |
F.A.Out(+,-) - Cable diameter | 1mm2~ 2.5mm2 |
F.A.Out(+,-) - Transmission distance | ≤1500m |
FAULT OUT (COM, NO) - Contact capacity | 30VDC@2A, 125VAC@0.5A |
FAULT OUT (COM, NO) - Recommended type of cable | Plain unscreened cable, 1.5mm2 |
FAULT OUT (COM, NO) - Cable diameter | 1mm2~ 2.5mm2 |
24VK (+, -) - Output voltage | 20 ~ 28VDC |
24VK (+, -) - Max. output current | 500mA, 1A S.C.Out+24VK in total |
24VK (+, -) - Recommended type of cable | Plain unscreened cable, 1.5mm2 |
24VK (+, -) - Cable diameter | 1mm2~ 2.5mm2 |
Loop Out (+, -) Loop In (+, -) - Output voltage | 18.5 ~ 28VDC, pulse |
Loop Out (+, -) Loop In (+, -) - Max. output current | 500mA |
Loop Out (+, -) Loop In (+, -) - Loop type | Class A and Class B |
Loop Out (+, -) Loop In (+, -) - Recommended type of cable | Unscreened twisted-pair, 1.5mm2 |
Loop Out (+, -) Loop In (+, -) - Max. Loop length | 2000m(Class A) |
Loop Out (+, -) Loop In (+, -) - Cable diameter | 1mm2~ 2.5mm2 |
RS-485 - Transmission rate | 9600 bps |
RS-485 - Recommended type of cable | Unscreened twisted-pair, 1mm2 |
RS-485 - Transmission distance | ≤1000m |
RS-485 - Cable diameter | 1mm2~ 2.5mm2 |
RS-485 - Max. number of panels | 20 |
CAN - Transmission rate | Optional: 10K, 20K, 50K and 100K bps |
CAN - Recommended type of cable | Unscreened twisted-pair, 1mm2 |
CAN - Transmission distance | ≤1000m |
Cable diameter | 1mm2~ 2.5mm2 |
Approx. Dimensions of the panel (W×H×D) | 400×360×104mm |
Approx. weight (without battery) | 3.7kg |
Operating conditions | Temperature range: -5°C~ 45°C; Max relative humidity: 95% (40°C ± 2°C, no condensation) |