Conventional Heat Detector C9020T
Features
- Designed with an upper cover and a lower cover, it can be installed, debugged and maintained conveniently.
- Within a MCU, it can monitor temperature of the site in real time.
- Non-polarity, two-bus connection that ensures convenient installation and maintenance.
- The detector is non-addressable.
Description
- C9020T point-type Conventional Rate of Rise and Fixed Temperature Heat Detector (De-tector hereunder) is a two-wire switch-type temperature-sensing detector. As a non-po-lar two-cables connection is adopted in the detector, it is compatible in conventional fire alarm control systems. The detector can be connected with addressable fire alarm con trol systems via the zone module.
The detector is applicable in places where fire might generate volume heat. e.g. in indus-trial and civil buildings such as in the kitchen, boiler room, generator room, drying plant,and smoking room.
Executive Standard | EN54-5 |
---|---|
Operating Voltage | DC24V(allowance:DC18V~30V) |
Workingcurrent | Standby current:<50uA @DC24V Alarm current:1mA~20mA @DC24V |
Wiringmethod | non-polar,twocables |
Indicators | During monitoring, the red indicator blinks once per 6 seconds.In sensor failure alarm, the red indicator blinks twice per 6 seconds. In fire alarm mode, the red indicator remains on. |
Weight | About 70g without base;about 105g with base DZ-912K |
Type of the Base | DZ-912K |
FixedTemperature | 64℃@A2S |
IngressProtection Rating | IP30 |
Related products
- Sanjiang
Combin Detector A9036T
- Sanjiang
Heat Detector A9020T
- Sanjiang
Isolation Module D9057M