A9020T point-type heat fire detector is a mated product of the SEC3002 fire alarm co ntrol panel. It uses a two-bus work mode. With an internal micro-processor, it support electronic coding. The detector realizes real-time acquisition of the in situ temperatur e data and sends back the data to a fire alarm control panel. It can also receive and exe cute the control commands given by a fire alarm control panel.
The detector is suitable for such industrial and civil buildings that have a great deal of heat when fire takes place, such as kitchens, boiler rooms, generator rooms, drying workshops and smoking rooms and is not suitable for places with a great deal of smoke but little heat.
| Operating Voltage | Loop 24V(18V~28V) |
|---|---|
| Standby Current | <0.3mA |
| Alarm Current | <1.5mA (without remote indicator) |
| Class | A2 |
| Fire LED | Red, Flash in polling, and illuminate in alarming. |
| Remote indicator output | Polarity-sensitive output, directly connect to remote indicator (built in 10k resistor in series, max. output current is 2mA); The red indicator will blink in the mon-itoring status or remain lit in the alarm status. |
| Programming | Electronically addressed. |
| Programming Range | Occupying one address within 1~324. |
| Wiring | Loop: two wire, polarity-insensitive |
| Environmental Temperature | -10℃~+50℃ |
| Relative Humidity | ≤95%, non-condensing |
| Material of Enclosure | ABS |
| Dimension | Diameter: 100mm |
| Mounting Hole Distance | 44.5mm~64.3mm |
| Weight | About 115g(with the base) |
Related products
- Sanjiang
Sounder Beacon A9091T
- Sanjiang
Manual Call Point A9060T
- Sanjiang
Conventional Sounder Beacon C9091T
- Sanjiang
IO Module A9056T



